Efficient and effective pipeline and fuel hydrant layout design including:
- Pipeline elevation profiles designed with 1:200 slopes for positive drainage to low points.
- Pipeline inspection vehicle launcher/receiver facility.
- Impressed current cathodic protection system for extended pipeline life.
- Full pipe-size return system (to allow re-filtering of product during low demand periods).
- Low point drain pits and high point vent pits positioned away from active apron areas.
- Hydrants in two branched zones; "B" branch can operate with shutdown in "A" branch.
- Automated system control valves in chambers positioned away from active apron areas.
- Emergency Shut Down system stations located adjacent to fuel hydrant positions.