Pipeline Distribution and Fuel Hydrant Outlets

Efficient and effective pipeline and fuel hydrant layout design including:

  • Pipeline elevation profiles designed with 1:200 slopes for positive drainage to low points.
  • Pipeline inspection vehicle launcher/receiver facility.
  • Impressed current cathodic protection system for extended pipeline life.
  • Full pipe-size return system (to allow re-filtering of product during low demand periods).
  • Low point drain pits and high point vent pits positioned away from active apron areas.
  • Hydrants in two branched zones; "B" branch can operate with shutdown in "A" branch.
  • Automated system control valves in chambers positioned away from active apron areas.
  • Emergency Shut Down system stations located adjacent to fuel hydrant positions.

Back to Profile.